PLC Digital Inputs of the Siemens S7-1200 - Types, Wiring and Troubleshooting

MSc. Jacob K. Biedulski 13 min read Updated

Digital inputs at first glance are a simple topic. PLCs use them to read the state of a signal - zero (FALSE) or one (TRUE). As a PLC programmer or automation system designer, you must have detailed knowledge about this.

There are a few aspects worth paying attention to:

  • Voltage levels of the digital input module (12 V, 24 V, 230 V, etc.)
  • Configuration of the input card as sink or source
  • Response time and contact bounce
  • High-speed digital inputs - HSC

Inputs in the control system

Controllers, such as the Siemens S7-1200 PLC, perform automation tasks through an operation cycle consisting of three key stages:

Reading inputs - The PLC reads the states of digital and analog inputs from sensors, switches, and other devices. In the Siemens S7-1200, both standard 24V digital signals and analog signals (e.g., 4-20 mA, 0-10 V, RTD) can be handled.

Processing the program - After reading the input data, the controller processes the stored program. The program, usually written in Ladder Logic (LAD), Function Block Diagrams (FBD), or Structured Text (ST), analyzes the input states and makes decisions that control the appropriate outputs.

Setting outputs - Based on the program logic, the PLC sends the appropriate signals to the outputs. The Siemens S7-1200 supports both digital and analog outputs, allowing control of various devices, from pneumatic actuators to inverters and servo drives.

In this article, we will focus on digital input signals because they form the foundation for the proper operation of the control system.

Various types of sensor devices and other elements that provide information about the state of the process or machine can be connected to the PLC inputs.

Here is a list of such devices:

Sensor TypeDescriptionSample Product
Proximity SensorsUsed to detect the presence of objects without physical contactProximity Sensor Sick Quasi-Flush IMB18-08BNOVC0S
Photoelectric SensorsUsed to detect objects based on changes in reflected or interrupted lightLight Beam Sensor Sick M40E-025023RB0
Temperature SensorsSuch as thermocouples or RTD sensors, which measure temperatureThermometer - Pt100 Resistance Sensor Endress+Hauser
Pressure SensorsMonitor pressure in pneumatic or hydraulic systemsWIKA A-1200 IO-Link Pressure Sensor
EncodersDevices used to measure rotational angle or linear positionTurck RE-10S6C Incremental Encoder
Limit SwitchesMechanical switching devices that activate when a machine element reaches a specified positionEaton LS-S11/RLA Limit Switch
Level SensorsUsed to detect the level of liquids or bulk materialsF&F PZP Liquid Level Float Probe
Micro SwitchesSmall switches activated by a slight physical forceCANAL MPH1512L17P Hermetic Micro Switch
Buttons and Manual SwitchesAllow operators to manually input commandsNO Control Button SP22-KLZ-11-230-BA9S

How does the Siemens S7-1200 PLC "see" digital signals?

Digital inputs on a PLC, such as those in the Siemens S7-1200 model, operate by detecting two voltage states corresponding to the logical levels "1" (high state) and "0" (low state). The controller interprets these signals based on the voltage applied to its input.

The controller processes these signals within its operating cycle, reading the input states in each scan cycle. The read values are stored in the controller's memory (in the so-called input memory map) and used for further processing by the control program.

For example, if a 24V voltage signal appears on a digital input, the controller will store a value of "1" for that input. If the signal drops to 0V, the controller will store a value of "0". In practice, this means that the controller is reading in real-time which devices are on (e.g., sensors, buttons) and which are off, controlling further actions accordingly, based on the stored program.

Low state (Low) - When the voltage at the input drops below a certain value (often below 5V or 0V), the controller reads this as a logical "0". This means that the input signal is inactive or off. In practice, if the sensor or switch on the input line does not provide voltage or the signal is zero, the controller interprets this as no signal.

High state (High) - When a voltage corresponding to the defined logical "1" level appears on the digital input (most often this is the VCC supply voltage, e.g., 24V DC in industrial systems), the controller recognizes that the input is active. For Siemens S7-1200, a voltage above a certain threshold (e.g., 15V) is usually interpreted as a logical "1".

Excerpt from the technical documentation of the S7-1200 1211C DC/DC/DC controller

Digital inputs in the S7-1200 PLC - galvanic isolation

The attached photo shows a fragment of the Siemens S7-1200 controller board, specifically the section responsible for digital inputs. The upper part of the board has a row of screw terminals used to connect signal wires responsible for introducing digital signals into the controller. These terminals enable connecting sensors, switches, and other peripheral devices that generate digital signals.

Galvanic isolation between the digital input section and the central processing unit (CPU) in the Siemens S7-1200 controller is a key element ensuring safe and reliable operation of the entire control system. This is achieved through the use of optoisolators, which act as an electrical barrier between the input signal circuits and the CPU logic circuits.

Optoisolators, also known as optocouplers, consist of two main components:

  • LED (on the input side),
  • Phototransistor (on the output side).

When a signal appears on the digital input, the current flowing through the LED causes it to light up. This light is detected by the phototransistor on the output side, which responds to the signal and transmits it to the CPU. The key aspect is that there is no direct electrical connection between the LED and the phototransistor - signal transmission occurs exclusively optically. This ensures that no electric current flows between the input section and the CPU, protecting the central unit from overvoltages, interference, or damage from external signal sources.

Digital inputs in PLC - response time and contact bounce

In Siemens PLCs, the response time to changes in the digital input state is crucial for the proper functioning of the system. One common issue encountered is contact bounce - brief, random signal changes that can occur with mechanical switches (e.g., relays) or buttons.

These bounces cause the signal to change multiple times in a short period before stabilizing, which can lead to incorrect readings by the controller.

In the Siemens S7-1200, we have the option of using input filters that eliminate these undesirable effects. By adjusting the filtering time, for example, setting it to a few milliseconds, the controller ignores short disturbances and only reacts to signals that persist for a specified time. The graph shows how contact bounce affects the input signal, and proper filter settings allow for stable readings without false state changes. Optimizing this parameter significantly improves the reliability of the control system.

PLC input types - Sink/Source

We distinguish between two types of inputs, which can be either "sink" or "source" inputs, depending on the configuration chosen and the type of sensors used in the project.

In Europe, PNP-type sensors and sink input cards are most commonly used. In Asia, however, the opposite approach prevails, where NPN-type sensors and source input cards are predominant.

Sink Inputs

In this case, the sensor supplies a 24V VCC potential to the controller (e.g., to DI a.0), and the digital input circuit is closed by connecting terminal 1M to ground (GND).

Source Inputs

Here, the circuit is closed by connecting terminal 1M to the power supply (VCC). The channel is activated when the sensor connects the input, e.g., on DI a.0, to a 0V (GND) potential.

Connecting buttons to sink/source inputs

Analyze the connection diagram of the Siemens S7-1200 CPU 1211C DC/DC/DC controller below. Note that you can configure the digital inputs in both sink and source modes, depending on how they are wired.

If you want to use inputs in sink configuration, you should connect the negative wire ("-" 0V) to terminal "M". In the source configuration, you should connect the positive wire ("+" 24V) to terminal "M". This flexibility allows the configuration to be adapted to the installation's needs and the type of peripheral devices, which may require different signal detection methods.

Inputs/Outputs of the S7-1200 1211C DC/DC/DC controller

Below are two ways to connect sensors to the controller. The first is a source sensor with a sink controller, and the second is the reverse - a sink sensor with a source controller. WARNING! A source sensor connected to a source controller will not work!

Ways to connect 3-wire sensors

High-Speed inputs (HSC)

In the Siemens S7-1200 controller, high-speed digital inputs (HSC - High-Speed Counters) are designed to handle high-frequency signals that standard digital inputs cannot accurately read due to timing limitations.

High-speed inputs (HSC) are particularly useful in applications such as speed measurement, pulse counting, reading encoder positions, or controlling precise processes requiring fast reactions.

Applications of high-speed inputs (HSC) in PLC S7-1200:

  • HTL Encoders: Used to measure the speed or position of motors and other devices.
  • Proximity Sensors: For quickly detecting objects in processing or packaging applications.

In the Siemens S7-1200 controller, two types of HSC (High-Speed Counter) channels are available, differing in the maximum signal reading frequency:

  1. High-Frequency HSC Channel - Handles signals up to 100 kHz. This is the main channel, designed for applications requiring high precision, such as counting pulses from encoders or high-speed sensors.
  2. Lower Frequency HSC Channel - Handles signals up to 30 kHz. This channel is used in less demanding applications where lower-frequency signals are sufficient.
Reading data from an encoder

Digital input modules

The S7-1200 controller offers built-in digital inputs and the possibility to expand the system with additional modules. The following digital input modules are available:

  • SM 1221 DI 8: Module with 8 digital inputs, operating voltage 24 VDC,
  • SM 1221 DI 16: Module with 16 digital inputs, operating voltage 24 VDC. (SM 1222 modules are digital output modules and SM 1223 modules combine inputs and outputs.)

These modules can be cascaded, increasing the number of available digital inputs in the system.

Learn the Siemens S7-1200 PLC programming language

Digital vs analog inputs and outputs in a PLC system

Every PLC system works with four basic signal groups. Understanding the difference between them makes it easier to choose the right PLC input module and to interpret signals from field devices:

  • Digital inputs (DI) - discrete on/off signals from push buttons, limit switches, proximity sensors and relay contacts. In industrial settings the most common level is 24 VDC; some PLC families also offer modules for AC voltage (120/230 VAC) for long cable runs.
  • Digital outputs (DQ) - output signals that switch output devices such as a relay, a contactor, a solenoid valve or an indicator lamp. Read more in our article on digital outputs in the Siemens S7-1200 PLC.
  • Analog inputs (AI) - continuous voltage or current signals, typically 0-10 V, ±10 V or 4-20 mA, from pressure, level or flow transmitters. The S7-1200 represents the nominal range as values from 0 to 27648, and you convert them to engineering units by scaling with NORM_X and SCALE_X.
  • Analog outputs (AQ) - setpoints for frequency inverters, proportional valves and other actuators.

Temperature measurement is a special case. Thermocouples deliver millivolt signals and RTDs (resistance temperature detectors) change their resistance, so they need specialized modules such as SM 1231 TC or SM 1231 RTD rather than a standard analog or digital input. See RTD sensors and the Siemens S7-1200 for a practical example.

Wiring PLC digital inputs - interfacing field devices

Correct wiring is the most important part of interfacing real-world input devices with the PLC. A few rules cover most cases:

  • 2-wire devices such as a push button or a mechanical limit switch are wired between the 24 VDC supply and the input terminal (sinking input), with the 1M terminal connected to 0 V.
  • 3-wire sensors (PNP or NPN) need power and a signal wire. For standard DC sensors, brown is +24 VDC, blue is 0 V and black is the switching output connected to the PLC input.
  • Use one low-voltage power supply for the sensors and the input group, or connect the reference potentials correctly. A missing 1M connection is a classic reason why no input reacts.
  • Separate signal cables from motor and power cables to limit interference on long runs.

For a deeper explanation of PNP and NPN wiring, read sinking vs sourcing PLC inputs and outputs.

Troubleshooting - why PLC digital inputs are not working

When the program does not see a signal, check the input from the field device to the program step by step:

  • Status LED - every onboard input of the S7-1200 has a status LED. If the LED is off, the problem is in the wiring or the sensor, not in the program.
  • Measure the voltage between the input terminal and M. For the S7-1200, a logical 1 requires at least 15 VDC, and a logical 0 is below 5 VDC.
  • Check the sensor type - an NPN sensor on a sinking input (or PNP on a sourcing input) will not switch the input.
  • 2-wire proximity sensors have a small leakage current that can keep an input in an undefined state. Check the sensor data sheet against the input specification.
  • Check the address - make sure the PLC tag in TIA Portal uses the right address, for example %I0.0, and that the hardware configuration matches the real module.
  • Input filter and scan time - a very short pulse may be filtered out or missed between two scans. Use a shorter filter time or an HSC channel for fast signals.
  • Watch table - monitor the input online in TIA Portal to confirm what the CPU really reads.

PLC digital inputs - FAQ

What is a digital input in a PLC?

A digital input is a PLC channel that reads a discrete signal with only two states, 0 (FALSE) or 1 (TRUE). It converts electrical signals from field devices, for example 24 VDC from a sensor, into a bit in the process image of the controller.

How many digital inputs does the Siemens S7-1200 have?

It depends on the CPU: the CPU 1211C has 6 digital inputs, the CPU 1212C has 8, and the CPU 1214C, 1215C and 1217C have 14. You can add more with signal boards and SM 1221 or SM 1223 modules.

What are typical PLC digital inputs and outputs examples?

Typical inputs are push buttons, selector switches, limit switches, proximity and photoelectric sensors and float switches. Typical outputs are contactor coils, relays, solenoid valves, indicator lamps and buzzers. To learn how to use these signals in a real program, check our Siemens TIA Portal LAD/FBD course.

Conclusion

When designing a system using the Siemens S7-1200 PLC, it is crucial to pay attention to several key aspects regarding digital inputs. Programming the Siemens S7-1200 PLC requires the proper selection of digital input voltage levels (12 V, 24 V, 230 V), as well as configuring inputs as sink or source, which affects how they are connected to sensors. Another important factor is optimizing the input response time and eliminating contact bounce to ensure accurate readings. For applications requiring fast signal processing, it is worth using high-speed digital inputs (HSC). These factors directly impact the reliability of a control system based on the Siemens S7-1200 PLC.

Author MSc. Jacob K. Biedulski

The ControlByte team - automation engineers who teach PLC programming on real projects.

Online courses

Want to program PLCs in practice?

Siemens, CODESYS, communication and safety courses with a certificate and instructor support. Start with a free mini-course.

See courses
Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • SKU
  • Rating
  • Price
  • Stock
  • Availability
  • Add to cart
  • Description
  • Content
  • Weight
  • Dimensions
  • Additional information
Click outside to hide the comparison bar
Compare